Squirrel Cage Induction Motor Testing(LT/Part1)
Type
Tests (as per IS 12615)
The following shall constitute type
tests:
a) Dimensions;
b) Measurement of resistance of windings of
stator;
c) No load test at rated voltage to determine input
current power and speed;
d) Reduced voltage running up test at no load
(for squirrel cage motors up to 37 kW only);
e) Locked rotor readings of voltage, current,
power input and torque at a suitable reduce
voltage;
f) Full load test to determine efficiency, power
factor and slip;
g) Temperature rise test;
h) Momentary overload test;
j) Insulation resistance test; and
k) High voltage test.
Optional
Tests(as per IS 12615)
The
optional tests shall be carried out as per the
mutual agreement between the manufacturer and the
purchaser.
a)
Test for vibration severity of motor;
b)
Test for noise levels of motor;
c)
Test for degree of protection by enclosure;
d)
Temperature rise test at limiting values of
voltage and frequency variation;
e) Over speed test; and
f) Test on insulation system.
Routine
Tests(as per IS 12615)
The following shall
constitute the routine tests:
a) Insulation
resistance test;
b) Measurement
of resistance of windings of
stator;
c) No
load test;
d) Locked
rotor readings of voltage, current and
power input at a suitable reduced voltage;
e) Reduced
voltage running up test; and
f) High
voltage test.
Routine
Tests(as per IEC 60034-1)
The following shall
constitute the routine tests:
a)Resistance
of windings (cold);
b)No-load
losses and current;
c)Direction
of rotation;
d)Withstand
voltage test;
The following shall constitute type tests:
a) Dimensions;
b) Measurement of resistance of windings of
stator;
c) No load test at rated voltage to determine input
current power and speed;
d) Reduced voltage running up test at no load
(for squirrel cage motors up to 37 kW only);
e) Locked rotor readings of voltage, current,
power input and torque at a suitable reduce
voltage;
f) Full load test to determine efficiency, power
factor and slip;
g) Temperature rise test;
h) Momentary overload test;
j) Insulation resistance test; and
k) High voltage test.
mutual agreement between the manufacturer and the
purchaser.
Motor Consumes 85% of Industrial Power

Wish aforesaid information shall help QA/Inspectors